Detuned Filter Reactor – A Series

Compare

Description

Detuned Filter Reactor – DELAB/ Made in Malaysia

Detuned Harmonic Circuit Filter Reactor is used for:

1) filtering harmonics and high frequency disturbance.
2) Reduce High inrush current (from parallel switching of capacitors & from power to capacitor banks and thus improves the operating source life span of the capacitor.
Filtering % p is the ratio of inductance to capacitance. It is not to be confused with the impedance or reactance of an inductor.

For a 50Hz system:
1) p=7% = 189Hz is used where protection to capacitor
and harmonics reduction is required.
2) p=6% = 204Hz is to be used where the system is rich
in 5th harmonics & above.
3)p=13% = 139Hz is used where voltage distortion
exceed permissible limit

1 Rated Voltage : 220, 380, 400, 415, 440, 480, 600, 690V 50 or 60Hz
2 Design Standard : IEC60076-6, 2007
3 Winding Material: Aluminum wire or Alu foil
4 Insulation Class : Class H, 180°
5 Insulation strength : 3.0KV 60s
6 Temperature Rise : 120°C max @ 40°C ambient as per IEC
7 Over-temp. Protection : 145°C bi-metal thermostat. Normally closed
8 Type of cooling : Natural Air Cool, AN
9 Protection : IP00, Indoor use
10 Core : Multiple gaps, high permeability, low loss silicon steel
11 Varnish : Epoxy based, vacuum impregnated and oven cured
12 Noise : Depend on size, usually less than 65db
13 Terminal Connection : Copper bus bar >20A, < 20A terminal blocks
14 Inductance tolerance ± 3%
15 Induction Linearity

( Ilin/ I1 )

P 14 = > 165%

P 8 = > 210%

P 7 = > 175%

P 5.67 = > 250%

16 Detuned factor, %P 5.67%, 7%, 8%, 14%
17 Output with capacitor, Qc KVAR 5-100KVAR
18 System Harmonic

Withstanding, %THDV

8% Max. as per EN50160 & IEC61000

With individual not exceeding the below :

V3 = 5.0%,  V5 = 6.0%,  V7 = 5.0%,  V9 = 1.5%,

V11=3.5% & V13 = 3.0%

*  Custom design available.